PVC electrical conduit

product details
PVC建筑绝缘电工套管.png


PVC electrical conduit quantitative Table of Large Thread

Wire specification

mm2

Φ25

Φ32

Φ40

Φ50

Φ63

1.0

16

26

45

69

110

1.5

14

23

39

61

99

2.5

10

16

28

42

69

4.0

8

13

22

34

56

6.0

6

10

18

26

43

10

3
5
9
1322
162
46
10
17
251
2
4
6
9
351
2
3
4
7
50
1
1
2
3
5














Main Performance Indicators of Products

Designed and manufactured as per International Electrotechnical Commission (IEC) standards such as IEC614, JG3050-1998 and British standards such as BS4607 and BS6099, the “JH” brand PVC insulated electrical insulation conduits are conforming to all the performance indexes. For high-impact heavy pipes (SGZH), the test results from China National Center for Quality Supervision & Test of Plastics Products (NTSQP) and indexes specified in IEC614 are compared as follows:


Items

Standard of IEC614 Heavy Pipe


Test Result of Jinghua Product

Appearance

Thesurface is smooth, and the wall thickness is equal. The external diameter ismeasured with the maximum and minimum external gauge.

Smooth

BendingProperty

Bending180° at roomtemperature and lowtemperature(-5℃or -15℃), thepipe has no damage or cracks can be seen on the surface.

Bending 180°at -15℃,there is no visible cracks.

CompressiveProperty

Load 1250N, uploading for one minute, the transformation<25%, unloading for one minute, the transformation<10%

Load 1250N, the uploading transformation is 5.6%, the unloading transformation is 2.4%.

ImpactProperty

At low temperature of -15℃ or -5℃, heavy punch 2kg, in height of 300mm, there is no visible cracks in at least 10 of the 12 samples.

At -15℃,heavy punch 2kg, in height of 300mm, there is no visible cracks in all the 12samples.

BendingFlat Property

Fixed in the 90° bend pipe of steel frame, in the oven of 60℃ ±2℃ for 24 hours, after taken out, the measure can pass through automatically.

Themeasure can pass through automatically.

Heat-resistantQuality

Underthe condition of 60℃,steelball with 5mm diameteris pressed by 20N on the pipe, the impression diameteron the pipe surface is <2mm.

Theimpression diameter is 1.2mm.

DielectricStrength

Whenthe water temperature is 23±5℃,voltage is AC2000V and frequency is 50Hz, it can keep non-breakdown for 15minutes.

Non-breakdown

InsulationResistance

Whenthe water temperature is 60±2℃andthe voltage is AC500V, the resistance >100 megohm.

2.8×102megohm

FlameRetardant Property

The test time in flame is as follows:
When the thickness of the material is ≤ 2.5mm, 2.5mm-3mm, it will be extinguished within 30 seconds after leaving the flame.
Time on the flames: placed 3 times successively at 25 seconds each time and   interval of 5 seconds, for 80 seconds.

Self-extinguishingwithin 3 seconds

Oxygen Index,Horizontal Firing, Vertical Firing

According to GB2406-80, GB2408-80 and GB4609-84 respectively

34GB2408-80/I class, satisfying the requirements of FU-0class












Characteristic of PVC electrical conduit

Strong resistance to pressure
Capable of bearing high pressure, both of high-impact heavy pipes (GY·415) and medium pipes (GY·315) can be paved in concrete via exposed and concealed paving without crack; the GY·415 series heavy pipes apply to concealed paving in compacted and vibrating concrete.

High resistance to corrosion and insects
PVC pipes are resistant to general acid and alkali and free from plasticizer to keep out insect.

Good fire resistance
The flame on PVC pipe can be knocked down quickly after leaving fire source to avoid fire spreading along with pipe. With low heat conductivity, the pipe can be well protected in case of fire, to ensure normal functioning of electric control system and personnel evacuating.

High insulation performance
The pipe can bear high voltage without breakdown, to avoid leakage and electric shock.

Simple construction
A.Light weight: With weight which is 1/5 that of steel pipe, the pipe can be easily transported and handled and installed with ease.

B.Easy bending: The pipe can be manually bent by inserting JHPI’s bending spring into the pipe.

C.Easy cut and connection: PVC pipes with diameter below φ32 mm can be easily cut off using JHPI’s cutter and then connected into the shapes needed using JHPI’s adhesive and accessories.

Lower investment

Material cost and construction and installation fees of PVC pipe are reduced greatly in comparison with steel pipes


Notice of Bending

■ Bend the pipe slowly to avoid damaging the pipe and its bending spring;

■Do not recover the bent pipe unless bending spring is taken out, to avoid damaging the spring;

■If failing to take out the bending spring, rotate the spring anticlockwise, pull it out and reduce its external diameter to take it out;

■For long pipes, tie the rope onto the hook at the end of bending spring, to pull out the spring after pipe is bent;

■For any construction at low temperature, do not bend the pipe until the bending position of pipe is heated through repeat friction using cloth.


xiangqing66.jpg

xiangqing04.jpg

Add.: No. 1, Jinghua Road, Xinglonggong Industrial Function Zone, Wen'an County
Tel:0316-5111365 5119265 5111665   008613831212656   008618103165488 Fax:0316-5112665   E-mail:leonwang@jinghua-china.com   Whatsapp:Facebook:008613831212656
            cindyzhang@jinghua-china.com   Whatsapp:Facebook:008618231630584 web:www.jhpi.cn
website qrcode

网站二维码